Data Sheet

Data sheet 3VA5222-6EC61-0AA0
circuit breaker 3VA5 UL frame 250 breaking capacity class H 65kA
@ 480V 2-pole, line protection TM230, FTAM, In=225A overload
protection Ir=225A fixed short-circuit protection Ii=5...10 x In without
connection
Model
Product brand name SENTRON
Product designation Molded-case circuit breaker
Product designation / according to UL file HFAS
Product version System protection
Design of the load switch / acc. to UL 489 / Heating,
Air Conditioning, and Refrigeration circuit breaker
(HACR Type)
Yes
Design of the overcurrent release TM230
Protective function of the overcurrent release LI
Number of poles 2
General technical data
Rated insulation voltage Ui 800V
Max. rated operational voltage Ue with AC 50/60Hz 690V
Max. rated operational voltage Ue with DC 500V
Power loss [W] / maximum 34.13W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
17.07W
Latching - endurance 20000
3VA5222-6EC61-0AA0 Subject to change without notice