Data Sheet

Electrical endurance (switching cycles) / at AC-1 / at
380/415 V 50/60 Hz
8000
Electrical endurance (switching cycles) / at 480 V / at
50/60 Hz
8000
Electrical endurance (switching cycles) / at 600 V / at
50/60 Hz
4000
Neutral conductors / upgradeable/retrofittable No
Ground fault monitoring version Without
Product function
● communication function
No
● other measurement function
No
Current
Max. rated operational current of the frame size 250A
Rated continuous current Iu 250A
Operating current
● at 40 °C
250A
● at 45 °C
244A
● at 50 °C
239A
● at 55 °C
233A
● at 60 °C
227A
● at 65 °C
222A
● at 70 °C
216A
Switching capacity according to IEC 60947
Design of short-circuit protection For switching power values in DC networks, see the 3VA molded
case circuit breaker device manual; link to be found under Service
& Support in the last chapter
Adjustable parameters
Adjustable response value current / li min. 2500A
Adjustable response value current / li max. 2500A
Ground fault protection / tripping switchable /
I2t=ON/OFF
No
Mechanical Design
Height [in] 7.3in
Height 185mm
Width [in] 4.1in
Width 105mm
Depth [in] 3.3in
Depth 83mm
Connections
Arrangement of electrical connectors / for main
current circuit
Without connection
Type of electrical connection / for main current circuit Without
3VA5225-0BB61-0AA0 Subject to change without notice
Page 2/
7