Data Sheet

Data sheet 3VA6210-5KP31-0AA0
circuit breaker 3VA6 UL frame 250 breaking capacity class M 35kA
@ 480V 3-pole, line protection ETU850, LSI, In=100A overload
protection Ir=40A...100A short-circuit protection Isd=0.6..10x In,
Ii=1.5..12x In N conductor protection optionally with external current
transformer, up to 160% without connection
Model
Product brand name SENTRON
Product designation Molded-case circuit breaker
Product designation / according to UL file MFAE-Y
Product version System protection
Design of the load switch / acc. to UL 489 / Heating,
Air Conditioning, and Refrigeration circuit breaker
(HACR Type)
Yes
Design of the overcurrent release ETU850
Protective function of the overcurrent release LSI
Number of poles 3
General technical data
Rated insulation voltage Ui 600V
Max. rated operational voltage Ue with AC 50/60Hz 600V
Power loss [W] / maximum 6.7W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
2.23W
Latching - endurance 20000
3VA6210-5KP31-0AA0 Subject to change without notice
Page 1/
8
07/13/2019 © Copyright Siemens