Data Sheet

Data sheet 3VA6225-7KT31-0AA0
circuit breaker 3VA6 UL frame 250 breaking capacity class C 100kA
@ 480V 3-pole, line protection ETU856, LSI, In=250A overload
protection Ir=100A...250A short-circuit protection Isd=0.6..10x In,
Ii=1.5..10x In N conductor protection optionally with external current
transformer, up to 160% ground-fault alarm message via EFB300 or
COM without connection
Model
Product brand name SENTRON
Product designation Molded-case circuit breaker
Product designation / according to UL file CFAE-Y
Product version System protection
Design of the load switch / acc. to UL 489 / Heating,
Air Conditioning, and Refrigeration circuit breaker
(HACR Type)
Yes
Design of the overcurrent release ETU856
Protective function of the overcurrent release LSI
Number of poles 3
General technical data
Rated insulation voltage Ui 600V
Max. rated operational voltage Ue with AC 50/60Hz 600V
Power loss [W] / maximum 42W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
14W
Latching - endurance 20000
3VA6225-7KT31-0AA0 Subject to change without notice
Page 1/
8
09/14/2019 © Copyright Siemens