Data Sheet

Data sheet 3VA6325-5KQ31-2AA0
circuit breaker 3VA6 UL frame 400 breaking capacity class M 35kA
@ 480V 3-pole, line protection ETU860, LSIG, In=250A overload
protection Ir=100A...250A short-circuit protection Isd=0.6..10x In,
Ii=1.5..12x In N conductor protection optionally with external current
transformer, up to 160% ground-fault protection Ig=0.2...1 x In,
tg=0.05-0.8s without connection
Model
Product brand name SENTRON
Product designation Molded-case circuit breaker
Product designation / according to UL file MJAE
Product version System protection
Design of the load switch / acc. to UL 489 / Heating,
Air Conditioning, and Refrigeration circuit breaker
(HACR Type)
Yes
Design of the overcurrent release ETU860
Protective function of the overcurrent release LSIG
Number of poles 3
General technical data
Rated insulation voltage Ui 600V
Max. rated operational voltage Ue with AC 50/60Hz 600V
Power loss [W] / maximum 27.3W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
9.1W
Latching - endurance 15000
3VA6325-5KQ31-2AA0 Subject to change without notice
Page 1/
8
09/14/2019 © Copyright Siemens

Summary of content (8 pages)