Data Sheet
Usage category A
Performance class for circuit breaker N
Mechanical service life (switching cycles) / typical 20000
Reference code / acc. to DIN 40719 extended
according to IEC 204-2 / acc. to IEC 750
Q
Operating frequency / maximum 1201/s
Voltage
Rated operational voltage Ue / max. 690V
Insulation voltage
● rated value
800V
● at AC / rated value
800V
Surge voltage resistance / rated value 8kV
Operating voltage
● rated value / maximum
690V
● for main current circuit / at AC / at 50 Hz / acc.
to UL 489 / maximum
600V
● for main current circuit / at AC / at 50 Hz /
maximum
690V
● for main current circuit / at AC / at 60 Hz / acc.
to UL 489 / maximum
600V
● for main current circuit / at AC / at 60 Hz /
maximum
690V
Protection class
Protection class IP IP20
Protective function of the overcurrent release LI
Current
Operating current / at 45 °C / rated value 65.1A
Continuous current / rated value 70A
Derating temperature / for the rated value of the
continuous current
50°C
● acc. to UL 489
40°C
Adjustable pick-up value current
● of the current-dependent overload release /
Full-scale value
70A
● of instantaneous short-circuit trip unit / initial
value
1000A
● of instantaneous short-circuit trip unit / Full-
scale value
1000A
Main circuit
Operating frequency
● 1 / rated value
50Hz
● 2 / rated value
60Hz
3VL1107-2KM30-0AA0 Subject to change without notice
Page 2/