Data Sheet

Surge voltage resistance / rated value 8kV
Operating voltage
● rated value / maximum
690V
● for main current circuit / at AC / at 50 Hz /
maximum
690V
● for main current circuit / at AC / at 60 Hz /
maximum
690V
Protection class
Protection class IP IP20
Protective function of the overcurrent release LSI
Current
Operating current / at 45 °C / rated value 1250A
Continuous current / rated value 1250A
Derating temperature / for the rated value of the
continuous current
50°C
Adjustable pick-up value current
● of the current-dependent overload release /
Full-scale value
1250A
● of instantaneous short-circuit trip unit / initial
value
1563A
● of instantaneous short-circuit trip unit / Full-
scale value
12500A
Main circuit
Operating frequency
● 1 / rated value
50Hz
● 2 / rated value
60Hz
Operating current
● at 40 °C / rated value
1250A
● at 50 °C / rated value
1250A
● at 55 °C / rated value
1187.5A
● at 60 °C / rated value
1187.5A
● at 65 °C / rated value
1000A
● at 70 °C / rated value
1000A
Auxiliary circuit
Number of CO contacts / for auxiliary contacts 0
Number of NC contacts / for auxiliary contacts 0
Number of NO contacts / for auxiliary contacts 0
Suitability
Suitability for use system/generator protection
Adjustable parameters
3VL7712-2UH36-0AA0 Subject to change without notice
Page 2/
4
09/13/2019 © Copyright Siemens