Data Sheet

Adjustable pick-up value current / of the short-time
delayed short-circuit release / Full-scale value
11250A
Adjustable pick-up value current / of the current-
dependent overload release / initial value
500A
Product details
Product component
● Trip indicator
No
● Auxiliary switch
No
● Voltage trigger
No
● undervoltage release
No
● undervoltage release with leading contact
No
Product extension / optional / motor drive Yes
Product function
Product function
● of thermal overload trip unit
adjustable
● Ground fault protection
No
● for neutral conductors / Short-circuit and
overload proof
No
● Overload protection
Yes
Short circuit
Operational short-circuit current breaking capacity
(Ics)
● at 240 V / rated value
50kA
● at 415 V / rated value
35kA
● at 500 V / rated value
30kA
● at 690 V / rated value
15kA
Maximum short-circuit current breaking capacity (Icu)
● at 240 V / rated value
100kA
● at 415 V / rated value
70kA
● at 440 V / rated value
50kA
● at 480 V / acc. to NEMA / rated value
50kA
● at 500 V / rated value
40kA
● at 600 V / acc. to NEMA / rated value
30kA
● at 690 V / rated value
30kA
Connections
Arrangement of electrical connectors / for main
current circuit
front side
Type of connectable conductor cross-sections
● for auxiliary contacts / solid
0.75 ... 1.5 mm²
● for auxiliary contacts / finely stranded / with
core end processing
0,75 ... 1.0 mm²
3VL7712-2UH36-0AA0 Subject to change without notice
Page 3/
4
09/13/2019 © Copyright Siemens