5.2.1.6 Troubleshooting
If a fault occurs, inspect the device for the following errors and take appropriate measures. If
there are other undefined errors, please contact Siemens Support (
https://
support.industry.siemens.com/cs/start?lc=en-US).
Error detection Cause of the error Troubleshooting
Device does not respond, all LEDs are
off
The device is not connected or the pow‐
er supply unit is not switched on.
Check the supply voltage of the device.
The red LED (RUN) flashes once per
second.
Undervoltage on the device Check the supply voltage of the device.
The yellow LED (RADIO) is off. Device is not connected to the Locating
Manager.
Switch on Locating Manager.
The blue LED (SERVER) is off. Device has no network connection
(LAN)
Check local network,
Check firewall
The blue LED (SERVER) flashes. Device is not connected to the Locating
Manager.
Activate Locating Manager
Anchors