User Manual
7/9
Building Technologies Division CC1N7714en
23.11.2017
Technical data
Degree of protection IP40
Safety class II
Mounting position Optional
Detector cable
- QRB1 Cable included in scope of delivery!
Stranded copper wire 2 x 0.75 mm²
Jacket 5.2 mm dia., PVC
Cable length according to «Type summary»
- QRB3 Cable to be supplied by thirds.
Recommended: H05VV-F 2 x 0.75
A
pplication standards should be observed.
Weight
- QRB1... (depending on type)
- QRB3... (without cable)
A
pprox. 20...35 g
A
pprox. 35 g
Storage DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+60 °C
Humidity <95 % r.h.
Transport DIN EN 60721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -20...+60 °C
Humidity <95 % r.h.
Operation DIN EN 60721-3-3
Climatic conditions Class 3K5
Mechanical conditions Class 3M2
Temperature range -20...+60 °C
Humidity <95 % r.h.
Installation altitude Max. 2,000 m above sea level
Caution!
Condensation, formation of ice and ingress of water are not permitted!
If not observed, the safety functions are no longer ensured and there will be a
risk of electric shock!
Function
Supervision of light radiation of oil flames in the visible range of the light spectrum.
The light-sensitive element is a photo resistor whose electrical dark resistance lies in
the M range.
As the intensity of light increases, the electrical resistance drops to the k range and is
evaluated by the burner control for generating the flame signal.
In contrast to the photocell ot the RAR, glowing firebrick in the combustion chamber
can be detected.
General detector data
Environmental
conditions