Datasheet

4AV Non-Stabilized Power Supplies
Filtered for Supply of Electronic Controls
SIRIUS 4AV2, 4AV4 power supplies,
filtered, single-phase
11/49
Siemens IC 10 · 2011
* You can order this quantity or a multiple thereof.
Illustrations are approximate
11
Overview
Rated output voltage U
2N
24 V DC
according to EN 61131-2
1)
and SIMATIC for input voltage
+6 % to –10 % and load 0 % to 100 %
Safety transformers according to EN 61558-2-6
4AV21, 4AV23:
C
U
US
at
60 °C,
¢
;
4AV20, 4AV22, 4AV24, 4AV26:
C
U
US
at
60 °C,
·
;
4AV41:
¢
•4AV2: t
a
= max. 60 °C/B,
4AV41: t
a
= 40 °C/B
Varistor suppressor circuit
Status LED
EMC according to EN 62041:
- 4AV2: Suitable for connection to the public supply (residen-
tial environments) and industrial networks (industrial
environments):
- 4AV4: Suitable for connection to industrial networks
(industrial environments)
Ripple < 5 %
For more products see Industry Mall and
Interactive Catalog CA 01 or www.mdexx.com
.
SIRIUS 4AV21, 4AV23 (left) and 4AV20, 4AV22 to 4AV24 (right) power
supplies
1)
EN 61131-2: equipment specification for power supply and interface for
programmable controllers. For limit values for 24 V DC see note on
Technical Information on page 11/1.
Selection and ordering data
Rated input voltage U
1N
1)
230 (240)-115 (120) V,
rated output voltage U
2N
24 V DC
C
U
US
,
¢
1)
During operation at the mains voltages listed in brackets, the upper limit for
24 V DC according to EN 61131-2 at +6 % mains voltage is met for a basic
load of 10 %. Under no-load operation, 30.6 V can be achieved.
2)
The delivery time class depends on the quantity, see page 11/5 "Options".
Rated input voltage U
1N
1)
400 (415) V,
rated output voltage U
2N
24 V DC
C
U
US
,
¢
1)
During operation at the mains voltages listed in brackets, the upper limit for
24 V DC according to EN 61131-2 at +6 % mains voltage is met for a basic
load of 10 %. Under no-load operation, 30.6 V can be achieved.
2)
The delivery time class depends on the quantity, see page 11/5 "Options".
Rated output current I
d
DT
2)
Screw terminals/
flat connectors
PU
(UNIT,
SET, M)
PS* PG Cu
weight
per PU
approx.
60 °C/B
EN 61558
CUUS
40 °C/B
EN 61558
Order No. Price
per PU
DC A DC A kg
Integrated standard rail mounting
1 1.2 } 4AV21 02-2EB00-0A 1 1 unit 104 0.600
3.5 4.2 } 4AV23 02-2EB00-0A 1 1 unit 104 0.900
Rated output current I
d
DT
2)
Screw terminals/
flat connectors
PU
(UNIT,
SET, M)
PS* PG Cu
weight
per PU
approx.
60 °C/B
EN 61558
CUUS
40 °C/B
EN 61558
Order No. Price
per PU
DC A DC A kg
Integrated standard rail mounting
1 1.2 } 4AV21 06-2EB00-0A 1 1 unit 104 0.600
3.5 4.2 } 4AV23 06-2EB00-0A 1 1 unit 104 0.900
IC10_11.book Seite 49 Donnerstag, 16. Dezember 2010 7:53 07
© Siemens AG 2010