Data Sheet for Product

F5000: Projected Beam Smoke Detector
6191
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety Products
Specialized Detection Devices
F5000 Reflective Optical Beam Smoke Detector
ARCHITECT AND ENGINEER SPECIFICATIONS
Range of 26.25 ft. to 330 ft.
(8.0 to 101 meters)
Modular design
Easy-fit mounting system
Ground-level system controller
LASER-assisted prism mounting
AutOptimise beam alignment
Electronic-obscuration test
Remote display and control unit with
liquid-crystal display (LCD) backlight
Contamination compensation
Building-shift compensation
Separate alarm and trouble contacts
Password-protected settings
Product Overview
The Reflective Beam Detector System (Model
F5000) from Siemens Fire Safety is an auto-
aligning, infrared-beam smoke detector. Once
the detector head is installed, an integral LASER
can be activated via the easy-fit mounting
system
that is aligned along the optical path of
the infrared beam. The LASER allows the
reflective prism to be quickly located.
The AutOptimise beam alignment system then
takes over, automatically steering and
maintaining the beam in the optimum position
for reliable performance. The signal that is
generated in the transmitter element and
reflected by the prism back to the receiver
element is analyzed for the presence of smoke.
The internal microprocessor determines an Alarm
condition when a pre-determined level is
reached.
The Projected Beam Smoke Detector is designed
to be mounted in a manner that allows the beam
to project between 1ft. (0.3m.) and 2ft. (0.61m.)
below, as well as project parallel to the ceiling.
Lateral detection may be up to 30ft. (9.1
4m.) on either
side of the beam, providing a maximum total coverage
area of up to 19,800 square feet (60 ft. [18.3m.] x
330 ft. [101m.]) Model F5000 can interface with
Siemens 50-point, 252-point and 504-point
addressable systems, as well as FireFinder® XLS/XLSV
Fire-Alarm Control Panels (FACPs), via the use of the
following Siemens modules: Models FDC
IO422, HTRI,
or HZM.
Specifications
The projected beam-type smoke detector is a 4-wire,
24 VDC device to be used with a
UL Listed and
separately supplied, (4) four-wire FACP. Model F5000
receives operating power by any
UL category ‘UTRZ’
power supply, such as the Siemens PAD-series NAC
extenders. Model F5000 is
UL268 Listed, and
consists of an integrated transmitter, receiver and
remote control unit. Model F5000 operates between
26.25 ft. to 330 ft. (8.0 to 101 meters).
Each unit includes a wall-mount remote display and
controller with LCD backlight.
Current monitoring for g
imbals motor position
User feedback of operating parameters
UL268 Listed;
CSF
M (
#
7260-1508:0104) Approved
Model
5000-017
Model
F5000

Summary of content (2 pages)