Product Description
The Component Kit (well not included) is designed
for installation into a 2-1/2-, 4-, or 6-inch well. The
sensor in the kit provides a temperature input to a
controller.
Contents
Description
Quantity
LB Box w/connector
1
Sensor
1
Transmitter
1
Sensor support tubes
3
Spring
1
Spring retaining washer
1
Wire nuts
4
Product Numbers
536-774-RK 4 to 20 mA, 20°F to 70°F
536-767-RK 4 to 20 mA, 30°F to 250°F
544-562-RK 4 to 20 mA, 0°C to 100°C
Required Tools
Medium flat-blade screwdriver
1-1/4-inch open end wrench or equivalent
adjustable wrench
Pliers or channel-locks
Wire stripper
Dow Corning #340 (or similar) thermal
compound
Expected Installation Time
28 minutes
Prerequisites
Read these instructions before beginning.
The immersion well(s) must be previously
installed and field wiring pulled to a
termination point near the well.
Installation
Installing a sensor assembly into a well
1. Disconnect one of the leads of the field wiring
from the termination board or block at the
controller.
2. Uncoil the sensor leads and remove the plug
from the well.
3. Select the appropriate length sensor support
tube for the well being serviced.
4. Assemble the spring and spring retaining washer
onto the sensor support tube and pass the lead
wires of the sensor through the tube. See
Figure 1.
Figure 1. Sensor Assembly.
5. Coat the sensor with thermal compound and
insert the assembly into the well.
6. Remove the cover and gasket from the LB box.
7. Wrap the treads of the connector installed on the
LB box with Teflon
®
tape or equivalent.
8. Thread the sensor leads through the connector
and out through the cover opening.
9. Screw the connector/LB box into the well.
10. Install wiring conduit, flex or rigid, between the
field utility box and the LB box.
11. Run field wiring through the conduit to the LB
box and connect the field wiring to the sensor
leads using the wire nuts provided.

Summary of content (2 pages)