Installation Instructions

Installation Instructions
Document No. 129-518
January 2, 2008
Immersion Well Temperature Sensors
Item Number 129-518, Rev. BA Page 1 of 2
Product Description
The Immersion Well Temperature Sensor provides a
temperature input to a controller. It threads into a
coupling on a piping system.
Figure 1. Immersion Sensor Installation.
Product Numbers
Product Number Sensing Element
544-577-XX
1K Platinum (375 α) RTD
536-777-XX
100K NTC
XX Insertion Length in Inches (mm)
25 2.5 (63.5)
40 4 (101.6)
60 6 (152.4)
Required Tools
Power screwdriver with 1/4-inch (6 mm) hex
extension or medium flat-blade screwdriver
1-1/4 inch (32 mm) open-end wrench or
equivalent adjustable wrench
Medium crescent wrench
Pipe sealant
Wire stripper
Expected Installation Time
3 hours
Prerequisites
The appropriate field wiring within the
maximum wiring run length for the individual
field panel or equipment controller must be in
place.
NOTE: All wiring must comply with National
Electric Code (NEC) and local
regulations.
A 1/2-inch (13 mm) NPT mounting coupling
must be installed in the piping system at the
sensor location. Figures 1 and 2 show two
types of installation in a pipe joint.
Instructions
NOTE: It is not recommended or necessary to
separate the well and the pulling elbow to
install the sensor assembly. The pulling
elbow should only be removed to replace a
damaged or defective sensing element.
1. Clean any dust away from the coupling for the
well.
2. Apply pipe sealant to the threads of the well and
insert the entire sensor assembly into the
coupling.
3. Hand-tighten the sensor assembly. Finish
tightening the assembly by using a 1-1/4 inch
(32 mm) open-end wrench. Tighten the
assembly until the outlet of the pulling elbow is
aligned with the controller.
4. Pull the field wiring to the pulling elbow and
connect the field wiring to the Sensing Element.
See Figure 4.
NOTE: In applications where condensate may
accumulate (chillers, low temperature
sensing, etc.) seal all wire connections
with RTV adhesive (ordered separately,
P/N 535-495).
5. Connect the field wiring at the controller.
The installation is now complete.