Operating Instructions

Chapter 3 Point Database
23
Siemens Industry, Inc. Owner's Manual 125-5069
2014-09-03
Descriptor
Address
1
Application
Description
the cooling air duct.
CLG FLO COEF 36 6665-6669 Calibration factor for the cold duct airflow sensor.
FLOW COEFF 1 36 6693 Calibration factor for air flow 1.
MTR3 COMD 37 6693 The value to which the Motor 3 actuator is commanded in
percent of full travel.
VALVE COMD {37} 6665-6669 The value to which the valve actuator is commanded in
percent of full travel for applications using a water valve.
MTR3 POS {38} 6693 The current position of the Motor 3 actuator in percent of full
travel. This value is calculated based on motor run time.
VALVE POS {38} 6665-6669 The current position of the valve in percent of full travel for
applications using a water valve. This value is calculated
based on motor run time. See
MTR3 TIMING
.
MTR3 TIMING 39 All The time, in seconds, required for the Motor 3 actuator to
travel from the full closed position to the full open position.
FAIL MODE 40 6665, 6666 Indicates the desired position of the dampers if the air flow
sensor(s) fail.
Valid input: CLOSED or OPEN.
DO 1 {41} All Digital output 1 controls a 24 Vac load with an ON or OFF
status. If Motor 1 is enabled, then DO 1 is coupled with DO 2
to control an actuator.
DO 2 {42} All Digital output 2 controls a 24 Vac load with an ON or OFF
status. If Motor 1 is enabled, then DO 2 is coupled with DO 1
to control an actuator.
DO 3 {43} All Digital output 3 controls a 24 Vac load with an ON or OFF
status. If Motor 2 is enabled, then DO 3 is coupled with DO 4
to control an actuator.
DO 4 {44} All Digital output 4 controls a 24 Vac load with an ON or OFF
status. If Motor 2 is enabled, then DO 4 is coupled with DO 3
to control an actuator.
DO 5 {45} All In applications with electric reheat, this digital output controls
the contact for the first stage of heating and has a status of
ON or OFF.
In applications with hot water reheat, this point is coupled
with DO 6 to control a hot water valve.
DO 6 {46} All In applications with electric reheat and CAL MODULE set to
NO, this output controls the contact for the second stage of
heating and has a status of ON or OFF.
In applications with hot water reheat, this point is coupled
with DO 5 to control a hot water valve.
DO 7 {47} All Digital output 7 controls a 24 Vac load with an ON or OFF
status.
In applications with CAL MODULE set to YES, this digital
output controls Autozero Module 1 for calibration of the
controller’s internal air velocity transducer that is piped to the
cold duct flow sensor.
In applications with electric reheat and CAL MODULE set to
NO, this digital output controls the contact for the third stage
of heating and has a status of ON or OFF.
CLG DMP CMD {48} 6665-6669 The value to which the cold duct damper motor is
commanded in percent of full travel.