Application

Sequence of Operation
Application Notes
14
Siemens Industry, Inc.
Application Note, App 6663
Application Notes
If temperature swings in the room are excessive or there is trouble maintaining the
room temperature setpoint, the temperature loop needs to be tuned.
If FLOW is oscillating while FLOW STPT is constant, then the flow loop requires
tuning.
The controller as shipped from the factory keeps all associated equipment OFF.
See the
Start-up
document for how to release the controller and its equipment to
application control.
Spare DOs can be used as auxiliary points that are controlled by the field panel
after being defined in the field panel's database. The combination of DO 3 and DO
4 may be used as auxiliary motor points. If using a pair of spare DOs to control a
motor, you must unbundle the corresponding motor command point.
For more information, contact your nearest Siemens Industry, Inc. representative.
Wiring Diagrams
NOTE:
The controller’s DOs control 24 Vac loads only. The maximum rating is 12 VA for
each DO. An external interposing relay is required for any of the following:
• VA requirements higher than the maximum
• 110 or 220 Vac requirements
• DC power requirements
• Separate transformers used to power the load
(for example part number 540-147, Terminal Equipment Controller Relay Module)
NOTE:
Thermistor inputs are 10K (default) or 100K software selectable (AUX TEMP AI X).
Wiring for AI with a 4 to 20 mA Sensor.