Application

Application 6663 Point Database
19
Siemens Industry, Inc.
Application Note, App 6663
Object
Type
1
Object
Instance
(Point
Number)
Object Name
(Descriptor)
Factory
Default
(SI Units)
2
Eng Units
(SI Units)
Range
Active Text
Inactive
Text
(SQ M)
AO
98
LOOP TIME
5
SEC
0-255
--
--
AO
{99}
ERROR STATUS
0
--
0-255
--
--
AO
{102}
AOV 1
0
VOLTS
0-10.23
--
--
AO
{103}
AOV 2
0
VOLTS
0-10.23
--
--
AO
{104}
AOV 3
0
VOLTS
0-10.23
--
--
AI
{105}
AI 3
0
PCT
0-102
--
--
AI
{106}
AI 4
74.0
(23.495556)
DEG F
(DEG C)
37.5-165
--
--
AO
107
RMTMP OFFSET
0.0 (0.0)
DEG F
(DEG C)
-31.75-32
--
--
BI
{108}
DI 4
OFF
--
Binary
ON
OFF
BI
{109}
DI 5
OFF
--
Binary
ON
OFF
BI
{110}
DI 6
OFF
--
Binary
ON
OFF
AO
111
STPT SPAN
0.0 (0.0)
DEG F
(DEG C)
0-63.75
--
--
AO
{121}
DEW POINT
-40.0 (-40.0)
DEG F
(DEG C)
-40-1598.35
--
--
AO
124
SENSOR SEL
0
--
0-255
--
--
AI
{125}
RM CO2
1000
PPM
0-8191
--
--
AI
{126}
RM RH
50
PCT
0-102
--
--
BO
{127}
PPCL STATE
EMPTY
--
Binary
LOADED
EMPTY
1)
Object Types are; Analog Input (AI), Analog Output (AO), Binary Input (BI) and Binary Output (BO).
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.