Application

Sequence of Operation
Control Temperature Setpoints
8
Siemens Industry, Inc.
Application Note, App 6663
CTL STPT Using Standard/Absolute Mode (Digital Room
Unit, Revision 26 and later)
Digital Room Unit (2200/2300 Series Firmware Revision 26 and later)
For all new digital room units, the value displayed and reported by the room unit is
linked to the current heat/cool mode. When the mode changes, the value is
automatically updated based on the new heat/cool mode.
When STPT SPAN is set to 0, the room setpoint adjustment on the digital room unit will
function in a standard mode. The range of the adjustment will be based on RM STPT
MIN and RM STPT MAX.
CTL STPT is set equal to RM STPT DIAL. The values for RM STPT MIN and RM
STPT MAX will be applied to limit RM STPT DIAL before it is copied into CTL STPT.
CTL STPT Using Warmer/Cooler Mode (Digital Room Unit,
Revision 26 and later)
Digital Room Unit (2200/2300 Series Firmware Revision 26 and later)
NOTE:
The warmer-cooler function is only available with BACnet PTEC controllers (standard
66xx apps).
When STPT SPAN is set to a value > 0, the room setpoint adjustment on the digital
room unit will function in a warmer/cooler mode. The range of the adjustment will be
calculated based on the current DAY CLG STPT or DAY HGT STPT and the STPT
SPAN value. This will allow the Room Setpoint Dial to be incremented up or down from
these setpoints by STPT SPAN.
CTL STPT is set equal to RM STPT DIAL. The values for RM STPT MIN and RM
STPT MAX will be applied to limit RM STPT DIAL before it is copied into CTL STPT.
When SPTP SPAN > 0, the minimum and maximum values for RM STPT DIAL are
calculated as follows:
Minimum lowest adjusted setpoint value is equal to DAY CLG STPT or DAY HTG
STPT - STPT SPAN
Maximum highest adjusted setpoint value is equal to DAY CLG STPT or DAY HTG
STPT + STPT SPAN
Example in Cooling Mode
If the STPT SPAN is set to 2.0 degrees, and the DAY CLG STPT is 76°F, you can step
up or down the room unit to adjust the RM STPT DIAL from 74°F to 78°F.