Assortment / System Description
Pneumatic Thermostats 
Powerstar® Single Setpoint Pneumatic Thermostat 192 S 
The 192 S Thermostats are proportional single output, single setpoint, 1-pipe (low air capacity) 
or  
2-pipe (high air capacity) sensor controllers. Each thermostat includes a wall mounting plate for 
installation in a variety of rough-in terminal boxes. A sensitive bimetal responds to temperature 
change to modulate control air through a flapper nozzle. One setpoint dial is provided. Air 
connections are made with 5/32” (4 mm) O.D. plastic tubing, directly to the thermostat chassis 
for retrofit applications or with plug-in adapter accessory that slide into the wall mounting plate. 
Part Numbers: 192-200, 192-201, 192-202, 192-203,192-220, 192-221, 192-222, 192-223 
Technical Instructions 
Installation Instructions 
Powerstar® Heating/Cooling Pneumatic Room Thermostat 192 HC 
The TH 192 HC thermostats are proportional single output, dual setpoint, 2-pipe (high air 
capacity) sensor controllers. Sensitive bimetals respond to temperature change to modulate 
control air through a flapper nozzle. When the supply air pressure changes from 18 to 25 psi 
(124 to 172 kPa), the thermostat automatically switches from the cooling to the heating setpoint 
respectively. Air connections are made with 5/32” (4 mm) O.D. plastic tubing, directly to the 
thermostat chassis for retrofit applications or with plug-in adapters which slide into the wall 
mounting plate. 
Part Numbers: 192-207, 192-208, 192-209, 192-210, 192-227, 192-228, 192-229, 192-230 
Technical Instructions 
Installation Instructions 
Powerstar® Day/Night/Vent Pneumatic Room Thermostat 192 DN/DNV 
The TH 192 DN and DNV thermostats are proportional single output, dual setpoint, 2-pipe or 
3-pipe (high air capacity) sensor controllers. Sensitive bimetals respond to temperature change 
to modulate control air through a flapper nozzle. When the supply air pressure changes from 18 
to 25 psi (124 to 172 kPa), the thermostat automatically switches from the day to the night 
setpoint respectively. Air connections are made with 5/32” (4 mm) O.D. plastic tubing, directly to 
the thermostat chassis for retrofit applications or with plug-in adapters which slide into the wall 
mounting plate. 
Part Numbers: 192-204, 192-205, 192-206, 192-224, 192-225, 192-226 
Technical Instructions 
Installation Instructions 
Powerstar® Free Energy Band Heating/Cooling Pneumatic Room 
Thermostat 193 HC 
The TH 193 HC thermostats are proportional dual output, dual setpoint, two-pipe (dual one-
pipe, low air capacity) or three-pipe (dual two-pipe, high air capacity) sensor controllers. 
Sensitive bimetals respond to temperature changes to modulate control air through a flapper 
nozzle. As the heating load decreases due to internal heat gains, a dead band of control 
minimizes energy consumption while the setpoint changes from 72°F (22°C) heating mode to 
78°F (26°C) cooling mode. Two setpoint dials allow adjustment of the dead band 4°F (2°C) 
minimum. Air connections are made with 5/32-inch (4 mm) O.D. plastic tubing, directly to the 
thermostat chassis for retrofit applications or with plug-in adapters which slide into the wall 
mounting plate. 
Part Numbers: 193-211, 193-212, 193-213, 193-214, 193-215, 193-216, 193-217, 193-218, 
193-235 
Technical Instructions 
Installation Instructions 
Powerstar® Free Energy Band Heating/Cooling Pneumatic Room 
Thermostat 193 HC Hesitation 
The TH 193 HC Hesitation Thermostats are proportional single output, dual setpoint, two-pipe 
(high air capacity) sensor controllers. Sensitive bimetals respond to temperature changes to 
modulate control air through a flapper nozzle. As the heating load decreases due to internal 
heat gains, a deadband of control minimizes energy consumption while the setpoint changes 
from 72°F (22°C) heating mode to 78°F (26°C) cooling mode. Two setpoint dials allow 
adjustment of the deadband (4°F, 2°C, minimum). Air connections are made with 5/32-inch (4 
mm) O.D. plastic tubing, directly to the thermostat chassis for retrofit applications or with plug-in 
adapters which slide into the wall mounting plate. 
Part Numbers: 193-219, 193-220 
Technical Instructions 
Installation Instructions 