Data Sheet for Product

Technical Specification Sheet
Document No. 149-855
November 04, 2015
Siemens Industry, Inc.
Page 1 of 6
BACnet Lab and Pressurized Room
Controllers with Off-board Air Modules
Lab Controller Module.
Off-board Air Module 550-819B.
The Laboratory Control Modules (LCMs) and
Pressurized Room Controllers (PRCs) have been
updated to share the same hardware and enhanced
applications on the new PTEC hardware platform.
These controllers use the Off-board Air Module
(OAM) to measure airflow for standard and custom
pressurized room control applications.
These controllers are designed to reside on any
BACnet control system.
NOTE:
The 570-8
xx
PA BACnet laboratory
controllers have new 67xx application
numbers. New application numbers may
require front-end graphics and reporting
modifications. Upgrading to the new
controllers might, in some rare
instances, cause some programming
rework.
Lab Controller Module
The LCM operates as an independent, stand-alone
DDC controller and can be connected on the Floor
Level Network (FLN). The LCM includes the largest
physical point count of any FLN device. Not all
physical points are used in all applications.
Off-board Air Module
The OAM contains the air velocity sensor (a
specialized differential pressure transducer), V/F
conversion circuitry and solenoid for auto-zero
function. Advanced digital signal processing produces
a highly accurate reading of even the noisiest flow
signals.
The auto-zero solenoid connects to the air velocity
pressure transducer's inlet ports to enable automatic
periodic re-calibration. This re-calibration ensures
accurate, drift-free airflow measurement. Automatic
re-calibration of the differential pressure transducers
occurs upon system power-up and when airflows are
stable with frequency selectable from 1 to 6 times a
day.