Data Sheet for Product

Predator VAV with CO2
Application Data Sheet
Predator VAV with CO2 Controller Configuration
Features
Demand Ventilation Control that adapts to meet IAQ specification requirements
Economizer control of outside air damper that provides energy savings
LonMark compliant with space-comfort controller functional profile (8502)
PID control minimizes offset and maintains tighter set point control to increase space comfort
Standby mode enables energy savings during occupied hours for rooms that are not always
used. When occupants are sensed, the controller quickly responds to maintain comfort levels.
Diversity control, through a demand limit input, maximizes comfort by maintaining even air
distribution to all zones during morning warm-up or pre-cool operation.
Conforms to the LonMark interoperability guidelines, enabling information sharing with LonMark
products from other vendors.
Sequence of Operation
In this core configuration, the Predator operates perimeter heat, the reheat coil and the primary air
damper to maintain required room temperature and ventilation conditions.
Occupied Mode
The Predator applies occupied settings for the space temperature setpoints and the primary air flow
minimum. The typical result is continuous ventilation, with heating or cooling automatically selected
to maintain comfort.
Cooling
The cooling PID maintains the measured space temperature at the occupied cooling setpoint by
modulating the primary air flow setpoint between the maximum cooling flow and the minimum
cooling flow.