Installation Instructions

Installation Instructions
Document No. 129-370
November 23, 2009
590 Series Differential Pressure Sensor
Item Number 129-370, Rev. DA Page 1 of 3
Product Description
The Series 590 Differential Pressure Sensors
convert differential pressure to a proportional
electronic output signal. They can be used with any
device that accepts a 0 to 10 Vdc or 4 to 20 mA
input.
Product Numbers
Product
Number
Percent
Accuracy
Pressure Range
Inches WC
(Water Column)
In
Conduit
Box
590-501 5
590-502 2
590-503 1
590-505
1% FS
± 0.25
No
590-506 5
590-507 2
590-508 1
590-510
1% FS
± 0.25
590-780 1
590-781 0.65
590-782
0.4% FS
0.5
Yes
Caution Notations
CAUTION:
Equipment damage or loss of data
may occur if you do not follow the
procedures as specified.
Required Tools
Wire strippers
1/8-inch flat-blade screwdriver
1/4-inch nut driver
Expected Installation Time
20 minutes
Prerequisites
Select a suitable location for mounting the
sensor.
Install field wiring, conduit to the sensor
location.
All wiring must be Class 2 and comply with
National Electric Code (NEC) and local
regulations.
Media Compatibility
590 Series sensors are designed to be used with air
or non-conducting gases.
CAUTION:
Use with liquids or corrosive gases will
damage the unit.
Environment
The operating and compensated temperature limits
are 0°F to 150°F (-18°C to 65°C).
Pressure Fittings
This unit has two factory-installed 1/4-inch OD
pressure fittings for the pressure signal connection
and typically installed with 1/4-inch push-on tubing.
Both the positive (high) pressure port and the
reference (low) pressure port are located on the
front of the unit, labeled HIGH and LOW,
respectively. For best results (shortest response
times), follow these guidelines:
Length
in Feet (Meters) Tubing
<100 (30) 3/16-inch ID
<300 (91) 1/4-inch ID
<900 (274) 3/8-inch ID