Install Instructions

Installation Instructions
Document No. 129-213
September 28, 2009
Diaphragm Replacement Kit for
Flowrite™ AP 599 Series 8-inch
Pneumatic Valve Actuator
Item Number 129-213, Rev. 200 Page 1 of 2
Product Description
This kit contains one diaphragm to replace the
diaphragm in a Flowrite AP 599 Series 8-inch
Pneumatic Valve Actuator.
Product Numbers
599-01060 Normal duty diaphragms
599-01061 High temperature diaphragms
Warning/Caution Notations
WARNING
Personal injury/loss of life may
occur if a procedure is not
performed as specified.
CAUTION
Equipment damage, or loss of
data may occur if the user
does not follow procedure as
specified.
Required Tools
1/2-inch socket or open end wrench
3/4-inch open end wrench
Expected Installation Time
50 minutes to replace actuator diaphragm
Prerequisites
Note the start point pressure before relieving the
spring tension.
WARNING:
Relieve all spring tension before removing
the actuator upper housing. See Step 2 in
Figure 1.
Installation
AP0156R1
3
2
1
3/4"
1/2"
Figure 1. Removing the Actuator Upper Housing.
AP0167R1
DIAPHRAGM
BEAD
DIAPHRAGM
GROOVE
Figure 2. Removing and Replacing the Diaphragm.
Make sure the new diaphragm bead fits in the
groove of the actuator lower housing.

Summary of content (2 pages)