Table 3. Maximum Water Capacity - U.S. Gallons per Minute.
Valve
Size
Inches
Pressure Differential - psi
Cv\1
2
3
4
5
6
8
10
15
20
25
30
40
50
60
75
1/2
0.4
0.6
0.7
0.8
0.9
1.0
1.1
1.3
1.5
1.8
2.0
2.2
2.5
2.8
3.1
3.5
0.63
0.9
1.1
1.3
1.4
1.5
1.8
2.0
2.4
2.8
3.2
3.5
4.0
4.5
4.9
5.5
1.0
1.4
1.7
2.0
2.2
2.5
2.8
3.2
3.9
4.5
5.0
5.5
6.3
7.1
7.8
8.7
1.6
2.3
2.8
3.2
3.6
3.9
4.5
5.1
6.2
7.2
8.0
8.8
10.1
11.3
12.4
13.9
2.5
3.5
4.3
5.0
5.6
6.1
7.1
7.9
9.7
11.2
12.5
13.7
15.8
17.7
19.4
22
4
5.7
7
8.0
8.9
10
11.3
12.6
15.5
17.9
20.0
21.9
25
28
31
35
3/4
6.3
8.9
10.9
12.6
14.1
15.4
17.8
20
24
28
32
35
40
45
49
55
1
10
14.1
17.3
20
22
24
28
32
39
45
50
55
63
71
77
87
Table 4. Maximum Water Capacity - Cubic Meters per Hour (m
3
/hr).
Valve Size
Pressure Differential - kPa
mm
1
10
20
30
40
50
60
80
Kvs/
100
150
200
300
400
500
15
0.03
0.11
0.15
0.19
0.22
0.24
0.26
0.30
0.34
0.42
0.48
0.59
0.68
0.76
0.05
0.17
0.24
0.30
0.34
0.38
0.42
0.48
0.54
0.66
0.76
0.94
1.08
1.21
0.09
0.27
0.38
0.47
0.54
0.60
0.66
0.76
0.85
1.0
1.2
1.5
1.7
1.9
0.14
0.43
0.61
0.75
0.87
0.97
1.06
1.23
1.37
1.7
1.9
2.4
2.7
3.1
0.21
0.68
0.96
1.17
1.35
1.51
1.66
1.91
2.15
2.6
3.0
3.7
4.3
4.8
0.34
1.1
1.5
1.9
2.2
2.4
2.7
3.1
3.4
4.2
4.9
6.0
6.9
7.7
20
0.54
1.7
2.4
3.0
3.4
3.8
4.2
4.9
5.4
6.7
7.7
9.4
10.9
12.1
25
0.86
2.7
3.8
4.7
5.4
6.1
6.7
7.7
8.6
10.5
12.2
14.9
17.2
19.2
32
1.4
4.4
6.2
7.6
8.7
9.8
10.7
12.3
13.8
16.9
19.5
23.9
27.6
30.9
40
2.2
6.8
9.6
11.8
13.6
15.2
16.7
19.2
22
26
30
37
43
48