Data Sheet

Shock acceleration 30gn
Vibrational acceleration / at 5 Hz ... 500 Hz / limited
to 2,5 h / per axis
7.5gn
Ambient temperature / during operation -40°C...80°C
Ambient temperature / during storage and transport -40°C...80°C
Relative humidity / during operation 5%...95%
Installation altitude / at height above sea level /
maximum
2000m
Width 53.4mm
Height 98.7mm
Depth 77.5mm
Net weight 525g
Electrical data
Type of distribution system TN-C
Operating voltage 240 / 415V AC
Operating voltage 230V
Continuous operating voltage
● maximum
335V
Load current 80 A
Protective conductor current 2400µA (255VAC)
Apparent power consumption / maximum 810mVA
Discharge current
● at (8/20) µs
12.5kA
● 1 phase / at (8/20) µs
50kA
● between L and (PE)N / at (8/20) µs
12.5kA
● between L and N / at (8/20) µs
50kA
Total discharge current / at (8/20) µs 150kA
Total lightning impulse current / at (10/350) µs 37.5kA
Lightning current peak value / at (10/350) µs 12.5kA
Charge of the lightning surge / at (10/350) µs 6.25A·s
Short-circuit rating (SCCR) / at 264 V 25kA
Protection level 1.2kV
● maximum
1.2kV
● between N and L
1.6kV
Residual voltage
● at rated value of discharge current / maximum
1.2kV
● at 10 kA maximum
1.1kV
● at 5 kA maximum
1kV
● at 3 kA / maximum
0.9kV
Response time 25ns
Settable response factor / of trip current 1.6
Fuse protection type / at V-shaped connection 80 A AC (gG)
Fuse protection type / for T-connector 160A AC (gG)