Data Sheet

Connections/Terminals
Type of electrical connection Screw terminal
Wire stripping length 16mm
Tightening torque 4.3...4.7
Wire stripping length 16mm
Connectable conductor cross-section
● for finely stranded conductor
1.5...25
● for rigid conductor
1.5...35
● finely stranded
1.5...25
AWG number / as coded connectable conductor
cross section
15...2
Design of the thread / of the connection screw M5
Signal design Optical, remote signaling contact
Indicator/remote signaling
Switching function / of the remote-signaling contacts PDT contact
Operating voltage / of the remote-signaling contacts
● at AC
5...250
● at DC
30V
Operating current / of the remote-signaling contacts
● at AC
5mA...1.5A
● at DC
1A DC (30V DC)
Connection type of remote signaling contact M2
Connectable conductor cross-section
● for remote signaling contacts / for rigid
conductor
0.14...1.5
● for finely stranded conductor / for remote
signaling contacts
0.14...1.5
AWG number / as coded connectable conductor
cross section / for remote signaling contacts /
minimum
28
AWG number / as coded connectable conductor
cross section / for remote signaling contacts /
maximum
16
Tightening torque / for remote signaling contacts 0.25N·m
Wire stripping length / of the cable / for remote
signaling contacts
7mm
NEMA/UL - Data
Type of distribution system TN-C
TOV behavior
● at TOV test voltage
415V AC (5s / withstand mode)
Combustibility class acc. to UL 94 V0
Further information
5SD7413-3 Subject to change without notice