Data Sheet
● for testing equipment / minimum
195V
Supply voltage frequency / rated value 50Hz
Protection class
Protection class IP IP20, if the distribution board is installed, with connected
conductors
Switching capacity
Breaking capacity short-circuit current (Icn) /
according to EN 61009-1 / rated value
10kA
Switching capacity current
● acc. to EN 60898 / rated value
10kA
● acc. to IEC 60947-2 / rated value
20kA
Rated residual switching capacity (IΔm) / according
to IEC 61009-1
10kA
Energy limiting class 3
Current
Tripping residual current / rated value 30mA
Tripping residual / rated value / derated current
● at 30 Cel
16A
● at 40 Cel
15.2A
● at 45 Cel
14.88A
● at 50 Cel
14.4A
● at 55 Cel
13.92A
● at 60 Cel
13.6A
● at 65 Cel
12.96A
● at 70 Cel
12.32A
Type of fault current A
Product details
Product function / neutral conductor switching Yes
Product feature / Touch protection Yes
Product feature
● halogen-free
Yes
● silicon-free
Yes
Connections
● Connectable conductor cross-section
— solid
0.75...35mm²
— stranded
0.75...35mm²
● Connectable conductor cross-section / finely
stranded / with core end processing
0.75...25mm²
Tightening torque / with screw-type terminals 2.5...3N·m
Position / of power supply cord Either top or bottom
5SU1324-6FA16 Subject to change without notice
Page 2/
5
09/13/2019 © Copyright Siemens