Data Sheet

● for testing equipment / minimum
195V
Supply voltage frequency / rated value 50Hz
Protection class
Protection class IP IP20, if the distribution board is installed, with connected
conductors
Switching capacity
Breaking capacity short-circuit current (Icn) /
according to EN 61009-1 / rated value
10kA
Switching capacity current
● acc. to EN 60898 / rated value
10kA
● acc. to IEC 60947-2 / rated value
20kA
Rated residual switching capacity (IΔm) / according
to IEC 61009-1
10kA
Energy limiting class 3
Dissipation
Power loss [W] / for rated value of the current / at AC
/ in hot operating state / per pole
1.8W
Current
Tripping residual current / rated value 30mA
Tripping residual / rated value / derated current
● at 30 Cel
10A
● at 40 Cel
9.5A
● at 45 Cel
9.3A
● at 50 Cel
9A
● at 55 Cel
8.7A
● at 60 Cel
8.5A
● at 65 Cel
8.2A
● at 70 Cel
8A
Type of fault current A
Product details
Product function / neutral conductor switching Yes
Product feature / Touch protection Yes
Product feature
● halogen-free
Yes
● silicon-free
Yes
Connections
● Connectable conductor cross-section
— solid
0.75...35mm²
— stranded
0.75...35mm²
● Connectable conductor cross-section / finely
stranded / with core end processing
0.75...25mm²