Data Sheet

Data sheet 5SV3346-6LA
Residual current operated circuit breaker, 4-pole, Type A, In: 63 A,
30 mA, Un AC: 400 V, with thermal overload protection
Model
Product brand name SENTRON
Product designation RCCB
Design of the product Instantaneous
Product variations With thermal overload protection
General technical data
Number of poles 4
Size of installation devices / acc. to DIN 43880 1
Protection against electrical shock Finger and back-of-hand safe
Short-circuit current rating 10kA
circuit-breaker / Design 5SV3
Mechanical service life (switching cycles) / typical 10000
Switching function / short-term delayed No
Overvoltage category III
Supply voltage
Current / at AC / rated value 63A
● Supply voltage / at AC / rated value
400 V
5SV3346-6LA Subject to change without notice