Data Sheet

● rated value
50 Hz
Protection class
Protection class IP IP20, if the distribution board is installed, with connected
conductors
Switching capacity
Switching capacity current / according to IEC 61008-
1 / rated value
0.8kA
Dissipation
Power loss [W] / for rated value of the current / at AC
/ in hot operating state / per pole
2.7W
Current
Tripping residual current / rated value 300mA
Tripping residual / rated value / derated current
● at 40 Cel
63A
● at 45 Cel
63A
● at 50 Cel
63A
● at 55 Cel
63A
● at 60 Cel
63A
● at 65 Cel
56.96A
● at 70 Cel
48.19A
Type of fault current A
I2t-value / permissible 110000A²·s
Surge current resistance / rated value 5kA
Operating frequency 50/60Hz
Product details
Product feature / silicon-free Yes
Product extension / can be installed / supplementary
devices
Yes
Connections
Connectable conductor cross-section
● solid
0.75...35mm²
● stranded
0.75...35mm²
Tightening torque / with screw-type terminals 2.5...3N·m
Position / of power supply cord top or bottom
Mechanical Design
Height 90mm
Width 36mm
Depth 70mm
Installation depth 70mm
Number of width units 2
5SV3616-8 Subject to change without notice
Page 2/
7
09/13/2019 © Copyright Siemens