Data Sheet

● rated value
50 Hz
Protection class
Protection class IP IP20, if the distribution board is installed, with connected
conductors
Switching capacity
Switching capacity current / according to IEC 61008-
1 / rated value
0.8kA
Dissipation
Power loss [W] / for rated value of the current / at AC
/ in hot operating state / per pole
2W
Current
Tripping residual current / rated value 300mA
Tripping residual / rated value / derated current
● at 40 Cel
40A
● at 45 Cel
38.1A
● at 50 Cel
35.59A
● at 55 Cel
32.29A
● at 60 Cel
28.19A
● at 65 Cel
23.3A
● at 70 Cel
17.62A
Type of fault current A
I2t-value / permissible 58000A²·s
Surge current resistance / rated value 1kA
Product details
Product feature / silicon-free Yes
Product extension / can be installed / supplementary
devices
Yes
Connections
Connectable conductor cross-section
● solid
0.75...35mm²
● stranded
0.75...35mm²
Tightening torque / with screw-type terminals 2.5...3N·m
Position / of power supply cord top or bottom
Mechanical Design
Height 90mm
Width 72mm
Depth 70mm
Installation depth 70mm
Number of width units 4
Mounting type DIN rail (REG)
5SV3644-6 Subject to change without notice