Data Sheet
Number of digital outputs 2
Short-circuit protection Yes
● Response threshold, typ.
4A
Limitation of inductive shutdown voltage to -55 to -60 V, typ. L+( )
Controlling a digital input Yes
Switching capacity of the outputs
● on lamp load, max.
5W
Load resistance range
● lower limit
12Ω
● upper limit
3400Ω
Output voltage
● for signal "1", min.
L+ (-1 V)
Output current
● for signal "1" rated value
2A
● for signal "1" permissible range, min.
7mA
● for signal "1" permissible range, max.
2.4A
● for signal "0" residual current, max.
0.5mA
Output delay with resistive load
● "0" to "1", max.
100µs
● "1" to "0", max.
400µs
Parallel switching of two outputs
● for uprating
No
● for redundant control of a load
Yes; per module
Switching frequency
● with resistive load, max.
100Hz
● with inductive load, max.
2Hz; 0,5 H
● on lamp load, max.
10Hz
Total current of the outputs
● Current per module, max.
4A
Cable length
● shielded, max.
1000m
● unshielded, max.
600m
Isochronous mode
Isochronous operation (application synchronized up
to terminal)
Yes
Interrupts/diagnostics/status information
Diagnostics function Yes; Can be read out
Substitute values connectable Yes; 0/1
Diagnostic messages
● Wire-break
Yes; channel by channel
● Short-circuit
Yes; channel by channel
Diagnostics indication LED
6AG1132-4BB31-7AB0 Subject to change without notice
Page 2/
4
09/15/2019 © Copyright Siemens