Data Sheet
● Group error SF (red)
Yes
● Status indicator digital output (green)
Yes
Parameter
Remark 3 byte
Diagnostics wire break Disable / enable
Diagnostics short-circuit Disable / enable
Response to CPU/master STOP Substitute a value/keep last value
Potential separation
Potential separation digital outputs
● between the channels
No
● between the channels and backplane bus
Yes
Isolation
Isolation tested with 500 V DC
Ambient conditions
Ambient temperature during operation
● min.
-25°C; = Tmin
● max.
70°C; = Tmax
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5000m
● Ambient air temperature-barometric pressure-
altitude
Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) //
Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500
m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5
000 m)
Relative humidity
● With condensation, tested in accordance with
IEC 60068-2-38, max.
100%; RH incl. condensation/frost (no commissioning under
condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according
to EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the
exception of fauna); Class 3B3 on request
— to chemically active substances according
to EN 60721-3-3
Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-
52 (severity degree 3); *
— to mechanically active substances
according to EN 60721-3-3
Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according
to EN 60721-3-6
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class
6B3 on request
— to chemically active substances according
to EN 60721-3-6
Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-
52 (severity degree 3); *
— to mechanically active substances
according to EN 60721-3-6
Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
6AG1132-4BB31-7AB0 Subject to change without notice
Page 3/