Data Sheet

Input current
Current consumption, max. 60mA; without load
Power loss
Power loss, typ. 1W
Address area
Address space per module
● Address space per module, max.
1byte; + 1 byte for QI information
Isochronous mode
Isochronous operation (application synchronized up
to terminal)
Yes
Bus cycle time (TDP), min. 500µs
Jitter, max. 8µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm
Yes
Diagnostic messages
● Monitoring the supply voltage
Yes
● Wire-break
Yes; channel by channel
● Short-circuit
Yes; channel by channel
● Group error
Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED)
Yes; Green PWR LED
● Channel status display
Yes; Green LED
● for channel diagnostics
Yes; Red LED
● for module diagnostics
Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels
No
● between the channels and backplane bus
Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-40°C; = Tmin (incl. condensation/frost)
6AG1132-6BD20-7CA0 Subject to change without notice
Page 2/
4
09/14/2019 © Copyright Siemens