Data Sheet
Rated value (DC) 24V
Encoder supply
Number of outputs 2
Short-circuit protection Yes; Electronic (response threshold 0.7 A to 2.1 A)
Output current
● up to 60 °C, max.
0.3A
24 V encoder supply
● 24 V
Yes; min. L+ (-1.5 V)
● Short-circuit protection
Yes
● Output current, max.
600mA; Total current of all encoders
Power
Power available from the backplane bus 70mW
Power loss
Power loss, typ. 5W
Address area
Address space per module
● Inputs
7byte
● Outputs
5byte
Digital inputs
Number of digital inputs 2
Source/sink input Yes; P-reading
Input characteristic curve in accordance with IEC
61131, type 1
Yes
Input voltage
● Type of input voltage
DC
● Rated value (DC)
24V
● for signal "0"
-30 to +5V
● for signal "1"
+15 to +30V
Input current
● for signal "1", typ.
3.7mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable
Yes
— at "0" to "1", min.
0.4ms
— at "0" to "1", max.
20ms
— at "1" to "0", min.
0.4ms
— at "1" to "0", max.
20ms
for technological functions
— parameterizable
No
Cable length
6AG1136-6PA00-2BC0 Subject to change without notice
Page 2/
5
09/13/2019 © Copyright Siemens