Data Sheet

● shielded, max.
1000m
● unshielded, max.
500m
Digital outputs
Number of digital outputs 1
Short-circuit protection Yes
Open-circuit detection Yes
● Response threshold, typ.
8mA
Overload protection Yes
● Response threshold, typ.
8.8A
Limitation of inductive shutdown voltage to max. 1.5 V
Switching capacity of the outputs
● with resistive load, max.
8A
● on lamp load, max.
100W
Load resistance range
● lower limit
3Ω
● upper limit
2000Ω
Output voltage
● for signal "1", min.
24V; L+ (-0.5 V)
Output current
● for signal "1" rated value
8A
● for signal "0" residual current, max.
1.5mA; PP-switching: max. 1.5 mA; PM-switching: max. 1 mA
Switching frequency
● with resistive load, max.
10Hz; Symmetrical
● with inductive load, max.
0.1Hz; according to IEC 60947-5-1, DC-13, symmetrical
● on lamp load, max.
4Hz; Symmetrical
Total current of the outputs
● Current per channel, max.
8A; Note derating data in the manual
● Current per module, max.
8A; Note derating data in the manual
Cable length
● shielded, max.
1000m
● unshielded, max.
500m
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable No
Alarms
● Diagnostic alarm
Yes
● Hardware interrupt
No
Diagnostics indication LED
● RUN LED
Yes; Green LED
● ERROR LED
Yes; Red LED
● Monitoring of the supply voltage (PWR-LED)
Yes; Green PWR LED
6AG1136-6PA00-2BC0 Subject to change without notice
Page 3/
5
09/13/2019 © Copyright Siemens