Data Sheet

Usage in industrial process technology
— Against chemically active substances acc.
to EN 60654-4
Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process,
measuring and control systems acc. to
ANSI/ISA-71.04
Yes; Level GX group A/B (excluding trichlorethylene; harmful gas
concentrations up to the limits of EN 60721-3-3 class 3C4
permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of
environmental conditions acc. to EN 60721,
EN 60654-4 and ANSI/ISA-71.04
* The supplied plug covers must remain in place over the unused
interfaces during operation!
Conformal coating
● Coatings for printed circuit board assemblies
acc. to EN 61086
Yes; Class 2 for high availability
● Protection against fouling acc. to EN 60664-3
Yes; Type 1 protection
● Military testing according to MIL-I-46058C,
Amendment 7
Yes; Discoloration of coating possible during service life
● Qualification and Performance of Electrical
Insulating Compound for Printed Board
Assemblies according to IPC-CC-830A
Yes; Conformal coating, Class A
Configuration
Programming
Programming language
— LAD
Yes
— FBD
Yes
— SCL
Yes
Cycle time monitoring
● adjustable
Yes
Dimensions
Width 110mm
Height 100mm
Depth 75mm
Weights
Weight, approx. 435g
last modified:
09/11/2019
6AG1214-1HG40-5XB0 Subject to change without notice
Page 8/
8
09/14/2019 © Copyright Siemens