Data Sheet
● Number of operating cycles, max.
mechanically 10 million, at rated load voltage 100 000
Cable length
● shielded, max.
500m
● unshielded, max.
150m
Analog inputs
Number of analog inputs 2
Input ranges
● Voltage
Yes
Input ranges (rated values), voltages
● 0 to +10 V
Yes
● Input resistance (0 to 10 V)
≥100k ohms
Cable length
● shielded, max.
100m; twisted and shielded
Analog outputs
Number of analog outputs 0
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
10bit
● Integration time, parameterizable
Yes
● Conversion time (per channel)
625µs
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
10bit
Encoder
Connectable encoders
● 2-wire sensor
Yes
1. Interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Protocols
● PROFINET IO Controller
Yes
● PROFINET IO Device
Yes; Also simultaneously with IO-Device functionality
PROFINET IO Controller
● Transmission rate, max.
100Mbit/s
6AG1214-1HG40-5XB0 Subject to change without notice
Page 4/
8