Data Sheet

Ambient conditions
Free fall
● Fall height, max.
0.3m; five times, in product package
Ambient temperature during operation
● min.
-40°C; = Tmin (incl. condensation/frost); start-up @ -25 °C
● max.
70°C; Tmax > 60 °C, derating: Max. one module may be
configured; this module must be the last module on the CM bus;
minimum clearance on the left side of at least 45 mm
Ambient temperature during storage/transportation
● min.
-40°C
● max.
70°C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5000m
● Ambient air temperature-barometric pressure-
altitude
Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) //
Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500
m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5
000 m)
Relative humidity
● Operation at 25 ℃ without condensation, max.
95%
● With condensation, tested in accordance with
IEC 60068-2-38, max.
100%; RH incl. condensation/frost (no commissioning under
condensation conditions)
Resistance
Coolants and lubricants
— Resistant to commercially available
coolants and lubricants
Yes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according
to EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the
exception of fauna); Class 3B3 on request
— to chemically active substances according
to EN 60721-3-3
Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-
52 (severity degree 3); *
— to mechanically active substances
according to EN 60721-3-3
Yes; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according
to EN 60721-3-6
Yes; Class 6B2 mold and fungal spores (excluding fauna); Class
6B3 on request
— to chemically active substances according
to EN 60721-3-6
Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-
52 (severity degree 3); *
— to mechanically active substances
according to EN 60721-3-6
Yes; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc.
to EN 60654-4
Yes; Class 3 (excluding trichlorethylene)
6AG1241-1CH32-2XB0 Subject to change without notice
Page 2/
3
09/13/2019 © Copyright Siemens