Data Sheet
— up to 60 °C, max.
5
vertical installation
— up to 40 °C, max.
5
Input voltage
● Rated value (DC)
24V
● for signal "0"
-3 to +5V
● for signal "1"
+15 to +30V
Input current
● for signal "1", typ.
8mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable
Yes; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of
the standard inputs during program runtime. Please note that
under certain circumstances your newly set filter time may not be
effective until the next filter cycle.)
— Rated value
3ms
for technological functions
— at "0" to "1", max.
48µs; Minimum pulse width/minimum pause between pulses at
maximum counting frequency
Cable length
● shielded, max.
1000m; 100 m for technological functions
● unshielded, max.
600m; for technological functions: No
for technological functions
— shielded, max.
100m; at maximum count frequency
— unshielded, max.
not allowed
Digital outputs
Number of digital outputs 6
● of which high-speed outputs
2; Notice: You cannot connect the fast outputs of your CPU in
parallel
integrated channels (DO) 6
Short-circuit protection Yes; Clocked electronically
● Response threshold, typ.
1A
Limitation of inductive shutdown voltage to L+ (-48 V)
Controlling a digital input Yes
Switching capacity of the outputs
● on lamp load, max.
5W
Load resistance range
● lower limit
48Ω
● upper limit
4kΩ
Output voltage
● for signal "1", min.
L+ (-0.8 V)
Output current
● for signal "1" rated value
500mA
6AG1312-5BF04-2AY0 Subject to change without notice