Data Sheet
Isolated No
Power supply to interface (15 to 30 V DC), max. 200mA
Protocols
● MPI
Yes
● PROFIBUS DP master
No
● PROFIBUS DP slave
No
● Point-to-point connection
No
MPI
● Transmission rate, max.
187.5kbit/s
Services
— PG/OP communication
Yes
— Routing
No
— Global data communication
Yes
— S7 basic communication
Yes
— S7 communication
Yes; Only server, configured on one side
— S7 communication, as client
No; but via CP and loadable FB
— S7 communication, as server
Yes
Communication functions
PG/OP communication Yes
Data record routing No
Global data communication
● supported
Yes
● Number of GD loops, max.
8
● Number of GD packets, max.
8
● Number of GD packets, transmitter, max.
8
● Number of GD packets, receiver, max.
8
● Size of GD packets, max.
22byte
● Size of GD packet (of which consistent), max.
22byte
S7 basic communication
● supported
Yes
● User data per job, max.
76byte
● User data per job (of which consistent), max.
76byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with
X_PUT or X_GET as server)
S7 communication
● supported
Yes
● as server
Yes
● as client
Yes; Via CP and loadable FB
● User data per job, max.
180byte; (with PUT/GET)
● User data per job (of which consistent), max.
240byte; as server
S5 compatible communication
● supported
Yes; via CP and loadable FC
Number of connections
6AG1312-5BF04-2AY0 Subject to change without notice
Page 8/
12
09/13/2019 © Copyright Siemens