Data sheet 6AG1313-5BG04-7AB0 SIPLUS S7-300 CPU 313C for medial exposure -25...+70°C based on 6ES7313-5BG04-0AB0 . Compact CPU with MPI, 24 DI/16 DO, 4 AI, 2 AO, 1 Pt100, 3 high-speed counters (30 kHz), Integr. power supply 24 V DC, work memory 128 KB, Front connector (2x 40-pole) and Micro Memory Card required General information Engineering with ● Programming package STEP 7 V5.5 + SP1 or higher or STEP 7 V5.
— Reverse polarity protection Yes Digital outputs — Rated value (DC) 24 V — Reverse polarity protection No Input current Current consumption (rated value) 650 mA Current consumption (in no-load operation), typ. 150 mA Inrush current, typ. 5A I²t 0.7 A²·s Digital inputs ● from load voltage L+ (without load), max. 80 mA Digital outputs ● from load voltage L+, max. 50 mA Power loss Power loss, typ.
● Number, max. 1 024; Number range: 0 to 7999 ● Size, max. 64 kbyte ● Number, max. 1 024; Number range: 0 to 7999 ● Size, max. 64 kbyte ● Description see instruction list ● Size, max.
Time range — lower limit 10 ms — upper limit 9 990 s IEC timer ● present Yes ● Type SFB ● Number Unlimited (limited only by RAM capacity) Data areas and their retentivity retentive data area in total All, max. 64 KB Flag ● Number, max.
● Outputs — of which central 1 008 1 008 Analog channels ● Inputs — of which central ● Outputs — of which central 253 253 250 250 Hardware configuration Number of expansion units, max. 3 Number of DP masters ● integrated none ● via CP 4 Number of operable FMs and CPs (recommended) ● FM 8 ● CP, PtP 8 ● CP, LAN 6 Rack ● Racks, max. 4 ● Modules per rack, max. 8; In rack 3 max.
Number of digital inputs ● of which inputs usable for technological functions 24 12 integrated channels (DI) 24 Input characteristic curve in accordance with IEC 61131, type 1 Yes Number of simultaneously controllable inputs horizontal installation — up to 40 °C, max. 24 — up to 60 °C, max. 12; up to 70 °C vertical installation — up to 40 °C, max. 12 Input voltage ● Rated value (DC) 24 V ● for signal "0" -3 to +5V ● for signal "1" +15 to +30V Input current ● for signal "1", typ.
Switching capacity of the outputs ● on lamp load, max. 5W Load resistance range ● lower limit 48 Ω ● upper limit 4 kΩ Output voltage ● for signal "1", min. L+ (-0.8 V) Output current ● for signal "1" rated value 500 mA ● for signal "1" permissible range, min. 5 mA ● for signal "1" permissible range, max. 0.6 A ● for signal "1" minimum load current 5 mA ● for signal "0" residual current, max. 0.
permissible input current for current input (destruction limit), max. 50 mA; Permanent No-load voltage for resistance-type transmitter, typ. 3.3 V Constant measurement current for resistance-type transmitter, typ. 1.
Current output, no-load voltage, max. 14 V Output ranges, voltage ● 0 to 10 V Yes ● -10 V to +10 V Yes Output ranges, current ● 0 to 20 mA Yes ● -20 mA to +20 mA Yes ● 4 mA to 20 mA Yes Connection of actuators ● for voltage output two-wire connection Yes; Without compensation of the line resistances ● for voltage output four-wire connection No ● for current output two-wire connection Yes Load impedance (in rated range of output) ● with voltage outputs, min.
● for inductive load 0.
● Series mode interference (peak value of interference < rated value of input range), min. 30 dB ● Common mode interference, min. 40 dB Interfaces Number of industrial Ethernet interfaces 0 Number of PROFINET interfaces 0 Number of RS 485 interfaces 1; MPI Number of RS 422 interfaces 0 1. Interface Interface type Integrated RS 485 interface Physics RS 485 Isolated No Power supply to interface (15 to 30 V DC), max.
● User data per job, max. 76 byte ● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) S7 communication ● supported Yes ● as server Yes ● as client Yes; Via CP and loadable FB ● User data per job, max. 180 byte; With PUT/GET ● User data per job (of which consistent), max.
Forcing ● Forcing Yes ● Forcing, variables Inputs, outputs ● Number of variables, max. 10 Diagnostic buffer ● present Yes ● Number of entries, max. 500 — adjustable No — of which powerfail-proof 100; Only the last 100 entries are retained ● Number of entries readable in RUN, max.
● between the channels No ● between the channels and backplane bus Yes Potential separation analog outputs ● Potential separation analog outputs Yes; common for analog I/O ● between the channels No ● between the channels and backplane bus Yes Permissible potential difference between different circuits 75 V DC/60 V AC Between the inputs and MANA (UCM) 8 V DC between MANA and M internally (UISO) 75 V DC/60 V AC Isolation Isolation tested with 600 V DC Standards, approvals, certificates CE ma
— to mechanically active substances according to EN 60721-3-3 Yes; Class 3S4 incl. sand, dust, * Use on ships/at sea — to biologically active substances according to EN 60721-3-6 Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request — to chemically active substances according to EN 60721-3-6 Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-252 (severity degree 3); * — to mechanically active substances according to EN 60721-3-6 Yes; Class 6S3 incl.
Depth 130 mm Weights Weight, approx.