Data Sheet

● Series mode interference (peak value of
interference < rated value of input range), min.
30dB
● Common mode interference, min.
40dB
Interfaces
Number of industrial Ethernet interfaces 0
Number of PROFINET interfaces 0
Number of RS 485 interfaces 1; MPI
Number of RS 422 interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated No
Power supply to interface (15 to 30 V DC), max. 200mA
Protocols
● MPI
Yes
● PROFIBUS DP master
No
● PROFIBUS DP slave
No
● Point-to-point connection
No
MPI
● Transmission rate, max.
187.5kbit/s
Services
— PG/OP communication
Yes
— Routing
No
— Global data communication
Yes
— S7 basic communication
Yes
— S7 communication
Yes; Only server, configured on one side
— S7 communication, as client
No; but via CP and loadable FB
— S7 communication, as server
Yes
Communication functions
PG/OP communication Yes
Data record routing No
Global data communication
● supported
Yes
● Number of GD loops, max.
8
● Number of GD packets, max.
8
● Number of GD packets, transmitter, max.
8
● Number of GD packets, receiver, max.
8
● Size of GD packets, max.
22byte
● Size of GD packet (of which consistent), max.
22byte
S7 basic communication
● supported
Yes
6AG1313-5BG04-7AB0 Subject to change without notice
Page 11/
16
09/13/2019 © Copyright Siemens