Data Sheet

Data sheet 6AG1315-2FJ14-2AB0
SIPLUS S7-300 CPU 315F-2PN/DP -25...+60°C with conformal
coating based on 6ES7315-2FJ14-0AB0 . Central processing unit
with 512 KB work memory, 1st interface MPI/DP 12Mbit/ s, 2nd
interface Ethernet PROFINET, with 2-port switch, Micro Memory
Card required
General information
Engineering with
● Programming package
STEP 7 V5.5 or higher, Distributed Safety V5.4 SP4
Supply voltage
Rated value (DC)
● 24 V DC
Yes
permissible range, lower limit (DC) 20.4V
permissible range, upper limit (DC) 28.8V
external protection for power supply lines
(recommendation)
2 A min.
Mains buffering
● Mains/voltage failure stored energy time
5ms
● Repeat rate, min.
1s
Input current
Current consumption (rated value) 750mA
Current consumption (in no-load operation), typ. 150mA
Inrush current, typ. 4A
I²t 1A²·s
6AG1315-2FJ14-2AB0 Subject to change without notice
Page 1/
15
09/14/2019 © Copyright Siemens