Data Sheet
Ambient temperature during storage/transportation
● min.
-40°C
● max.
70°C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
2000m
● Ambient air temperature-barometric pressure-
altitude
Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
● With condensation, tested in accordance with
IEC 60068-2-38, max.
100%; RH incl. condensation/frost (no commissioning under
condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according
to EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the
exception of fauna); Class 3B3 on request
— to chemically active substances according
to EN 60721-3-3
Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-
52 (severity degree 3); *
— to mechanically active substances
according to EN 60721-3-3
Yes; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according
to EN 60721-3-5
Yes; Class 5B2 mold, fungus and dry rot spores (with the
exception of fauna); Class 5B3 on request
— to chemically active substances according
to EN 60721-3-5
Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 50155
(ST2); *
— to mechanically active substances
according to EN 60721-3-5
Yes; Class 5S3 incl. sand, dust; *
Remark
— Note regarding classification of
environmental conditions acc. to EN 60721,
EN 60654-4 and ANSI/ISA-71.04
* The supplied plug covers must remain in place over the unused
interfaces during operation!
Configuration
Configuration software
● STEP 7
Yes; V5.2 SP1 or higher with HW update
Programming
● Command set
see instruction list
● Nesting levels
8
● System functions (SFC)
see instruction list
● System function blocks (SFB)
see instruction list
Programming language
— LAD
Yes
— FBD
Yes
— STL
Yes
— SCL
Yes
— CFC
Yes
6AG1315-6FF04-2AY0 Subject to change without notice
Page 10/
11
09/13/2019 © Copyright Siemens