Data Sheet
Switching capacity of the outputs
● on lamp load, max.
5W
Output current
● for signal "1" rated value
2A
● for signal "1" permissible range for 0 to 40 °C,
min.
7mA
● for signal "1" permissible range for 0 to 40 °C,
max.
2.4A
● for signal "1" permissible range for 40 to 60 °C,
min.
7mA
● for signal "1" permissible range for 40 to 60 °C,
max.
2.4A
● for signal "0" residual current, max.
0.5mA
Switching frequency
● with resistive load, max.
25Hz
● with inductive load, max.
25Hz
● on lamp load, max.
10Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.
10A
— up to 60 °C, max.
6A
vertical installation
— up to 40 °C, max.
5A
Cable length
● shielded, max.
1000m
● unshielded, max.
600m
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm
Yes
Diagnostic messages
● Diagnostic information readable
Yes
Diagnostics indication LED
● Fail-safe operation
Yes
● Group error SF (red)
Yes
Potential separation
Potential separation digital outputs
● between the channels
Yes
● between the channels, in groups of
5
● between the channels and backplane bus
Yes
● between the channels and the power supply of
the electronics
Yes
6AG1326-2BF10-2AB0 Subject to change without notice