Data Sheet

Input ranges
● Voltage
Yes
● Current
Yes
● Thermocouple
Yes
● Resistance thermometer
Yes
● Resistance
Yes
Input ranges (rated values), voltages
● 0 to +10 V
No
● 1 V to 5 V
Yes
● Input resistance (1 V to 5 V)
100kΩ
● 1 V to 10 V
No
● -1 V to +1 V
Yes
● Input resistance (-1 V to +1 V)
10MΩ
● -10 V to +10 V
Yes
● Input resistance (-10 V to +10 V)
100kΩ
● -2.5 V to +2.5 V
Yes
● Input resistance (-2.5 V to +2.5 V)
100kΩ
● -250 mV to +250 mV
Yes
● Input resistance (-250 mV to +250 mV)
10MΩ
● -5 V to +5 V
Yes
● Input resistance (-5 V to +5 V)
100kΩ
● -50 mV to +50 mV
No
● -500 mV to +500 mV
Yes
● Input resistance (-500 mV to +500 mV)
10MΩ
● -80 mV to +80 mV
Yes
● Input resistance (-80 mV to +80 mV)
10MΩ
Input ranges (rated values), currents
● 0 to 20 mA
Yes
● Input resistance (0 to 20 mA)
25Ω
● -10 mA to +10 mA
Yes
● Input resistance (-10 mA to +10 mA)
25Ω
● -20 mA to +20 mA
Yes
● Input resistance (-20 mA to +20 mA)
25Ω
● -3.2 mA to +3.2 mA
Yes
● Input resistance (-3.2 mA to +3.2 mA)
25Ω
● 4 mA to 20 mA
Yes
● Input resistance (4 mA to 20 mA)
25Ω
Input ranges (rated values), thermocouples
● Type B
No
● Type C
No
● Type E
Yes
6AG1331-7KF02-2AB0 Subject to change without notice
Page 2/
6
09/13/2019 © Copyright Siemens