Data Sheet

Interrupts/diagnostics/status information
Diagnostics function Yes; Parameterizable
Alarms
● Diagnostic alarm
Yes; Parameterizable, channels 0 and 2
● Limit value alarm
Yes; Parameterizable
Diagnostic messages
● Diagnostic information readable
Yes
Diagnostics indication LED
● Group error SF (red)
Yes
Potential separation
Potential separation analog inputs
● between the channels and backplane bus
Yes
Isolation
Isolation tested with 500 V DC
Standards, approvals, certificates
CE mark Yes
UL approval Yes; File E239877
RCM (formerly C-TICK) Yes
KC approval Yes
EAC (formerly Gost-R) Yes
Railway application
● EN 50121-4
No
● EN 50155
Yes; Sections 4, 5 and 12; no further agreements apply; T1,
Category 1, Class A/B, EN 50155:2007
Ambient conditions
Ambient temperature during operation
● min.
-25°C; = Tmin
● max.
70°C; = Tmax; for use on railway vehicles according to EN50155,
the rated temperature range -25 ... +55 °C (T1) or 60 °C @
UL/ULhaz/ATEX/FM use applies
Ambient temperature during storage/transportation
● min.
-40°C
● max.
70°C
Altitude during operation relating to sea level
● Installation altitude above sea level, max.
5000m
● Ambient air temperature-barometric pressure-
altitude
Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) //
Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500
m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5
000 m)
Relative humidity
● With condensation, tested in accordance with
IEC 60068-2-38, max.
100%; RH incl. condensation/frost (no commissioning under
condensation conditions)
6AG1331-7KF02-2AB0 Subject to change without notice