Data Sheet

Load impedance (in rated range of output)
● with current outputs, max.
750Ω
● with current outputs, inductive load, max.
10mH
Cable length
● shielded, max.
800m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.
16bit
Settling time
● for resistive load
0.1ms
● for inductive load
0.5ms
Errors/accuracies
Operational error limit in overall temperature range
● Current, relative to output range, (+/-)
0.2%; ±0.4 % @ < 0 °C or > 60 °C
Basic error limit (operational limit at 25 °C)
● Current, relative to output range, (+/-)
0.1%
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm
Yes
Diagnostic messages
● Diagnostic information readable
Yes
Diagnostics indication LED
● Group error SF (red)
Yes
Potential separation
Potential separation analog outputs
● between the channels and backplane bus
Yes
Isolation
Isolation tested with 500 V DC
Standards, approvals, certificates
CE mark Yes
UL approval Yes; File E239877
RCM (formerly C-TICK) Yes
KC approval Yes
EAC (formerly Gost-R) Yes
Ambient conditions
Ambient temperature during operation
● min.
-25°C; = Tmin
6AG1332-8TF01-2AB0 Subject to change without notice
Page 2/
4