Data sheet 6AG1412-5HK06-7AB0 SIPLUS S7-400 CPU 412-5H -25...+70°C with conformal coating based on 6ES7412-5HK06-0AB0 . Central processing unit for S7400H and S7-400F/FH, 5 interfaces: 1x MPI/DP, 1x DP, 1x PN and 2 for SYNC modules, 1 MB memory (512 KB data/512 KB program) General information Product type designation CPU 412-5H PN/DP HW functional status 1 Firmware version V6.0 Engineering with ● Programming package As of STEP 7 V5.
from interface 5 V DC, max. 90 mA; At each DP interface Power loss Power loss, typ. 7.5 W Memory Type of memory RAM Work memory ● integrated 1 Mbyte ● integrated (for program) 512 kbyte ● integrated (for data) 512 kbyte ● expandable No Load memory ● expandable FEPROM Yes; with Memory Card (FLASH) ● expandable FEPROM, max. 64 Mbyte ● integrated RAM, max. 512 kbyte ● expandable RAM Yes ● expandable RAM, max.
● Number, max. 3 000; Number range: 0 to 7999 ● Size, max. 64 kbyte ● Number, max. see instruction list ● Size, max.
— upper limit 9 990 s IEC timer ● present Yes ● Type SFB ● Number Unlimited (limited only by RAM capacity) Data areas and their retentivity retentive data area in total Total working and load memory (with backup battery) Flag ● Number, max. 8 192 byte ● Retentivity available Yes ● Retentivity preset MB 0 to MB 15 ● Number of clock memories 8; in 1 memory byte Local data ● adjustable, max.
Multicomputing No Interface modules ● Number of connectable IMs (total), max. 6 ● Number of connectable IM 460s, max. 6 ● Number of connectable IM 463s, max. 4; Single mode only Number of DP masters ● integrated 2 ● via CP 10; CP 443-5 Extended ● Mixed mode IM + CP permitted No ● via interface module 0 Number of IO Controllers ● integrated 1 ● via CP 0 Number of operable FMs and CPs (recommended) ● FM See manual Automation System S7-400H fault-tolerant systems.
● on Ethernet via NTP Yes; As client Time difference in system when synchronizing via ● Ethernet, max. 10 ms; Via NTP ● MPI, max. 200 ms Interfaces Number of RS 485 interfaces 2 Number of other interfaces 2; Fiber-optic interface 1. Interface Interface type Integrated Physics RS 485 / PROFIBUS + MPI Isolated Yes Power supply to interface (15 to 30 V DC), max.
— S7 communication, as server Yes — Equidistance No — Isochronous mode No — SYNC/FREEZE No — Activation/deactivation of DP slaves No — Direct data exchange (slave-to-slave communication) No — DPV1 Yes Address area — Inputs, max. 2 kbyte — Outputs, max. 2 kbyte User data per DP slave — User data per DP slave, max. 244 byte — Inputs, max. 244 byte — Outputs, max. 244 byte — Slots, max. 244 — per slot, max.
● Web server No ● Point-to-point connection No PROFINET IO Controller ● Transmission rate, max. 100 Mbit/s Services — PG/OP communication Yes — S7 routing Yes — S7 communication Yes — Isochronous mode No — Open IE communication Yes — Shared device Yes; Single mode only — Prioritized startup No — Number of connectable IO Devices, max. 256; In redundant mode via both interfaces — Number of connectable IO Devices for RT, max. 256 — of which in line, max.
● Transmission rate, max. 12 Mbit/s ● Number of DP slaves, max. 64 Services — PG/OP communication Yes — Routing Yes — Global data communication No — S7 basic communication No — S7 communication Yes — S7 communication, as client Yes — S7 communication, as server Yes — Equidistance No — Isochronous mode No — SYNC/FREEZE No — Activation/deactivation of DP slaves No — Direct data exchange (slave-to-slave communication) No — DPV0 Yes — DPV1 Yes Address area — Inputs, max.
— Data length, max. 32 kbyte — several passive connections per port, supported Yes ● ISO-on-TCP (RFC1006) Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs — Number of connections, max. 46 — Data length, max. 32 kbyte; 1452 bytes via CP 443-1 Adv. ● UDP Yes; via integrated PROFINET interface and loadable FBs — Number of connections, max. 46 — Data length, max.
● overall 48 ● usable for PG communication — reserved for PG communication 1 — adjustable for PG communication, max. 0 ● usable for OP communication — reserved for OP communication 1 — adjustable for OP communication, max. 0 ● usable for S7 basic communication — reserved for S7 basic communication 0 — adjustable for S7 basic communication, max. 0 ● usable for S7 communication — reserved for S7 communication 0 — adjustable for S7 communication, max.
Forcing ● Forcing Yes ● Forcing, variables Inputs/outputs, bit memories, distributed I/Os ● Number of variables, max. 256 Diagnostic buffer ● present Yes ● Number of entries, max. 3 200 — adjustable Yes — preset 120 Service data ● can be read out Yes EMC Emission of radio interference acc.
— to mechanically active substances according to EN 60721-3-3 Yes; Class 3S4 incl. sand, dust, * Use on ships/at sea — to biologically active substances according to EN 60721-3-6 Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request — to chemically active substances according to EN 60721-3-6 Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-252 (severity degree 3); * — to mechanically active substances according to EN 60721-3-6 Yes; Class 6S3 incl.
— GRAPH Yes — HiGraph® Yes Number of simultaneously active SFCs — RD_REC 8 — WR_REC 8 — WR_PARM 8 — PARM_MOD 1 — WR_DPARM 2 — DPNRM_DG 8 — RDSYSST 8 — DP_TOPOL 1 Number of simultaneously active SFBs — RDREC 8 — WRREC 8 Know-how protection ● User program protection/password protection Yes ● Block encryption Yes; With S7 block Privacy Dimensions Width 50 mm Height 290 mm Depth 219 mm Weights Weight, approx.